beautypg.com

Performance data – Trane WSC060-120 User Manual

Page 31

background image

PKGP-PRC004-EN

31

Performance
Data

Table PD-22 - Static Pressure Drops Through Accessories - (Pascals)

Econimizer with

Electric Heater

OA/RA Dampers

2

Accessory (kW)

3

Unit

Airflow

Standard

Pleated Filters

100% OA

100% RA

100% OA

100% RA

7-9

10-27

37-40

Model No.

(m

3

/h)

Filters

1

50 mm (2 inch)

Downflow

Horizontal

2720

25

37

30

11

30

4

11

13

WSC060AD,T

3400

37

55

46

17

46

6

17

21

4080

55

72

64

26

64

9

25

30

3260

10

17

25

2

15

5

5

WSC072AD,T

4080

15

22

27

5

20

5

8

4890

22

30

33

10

25

10

13

4080

15

22

27

5

20

5

8

WSC090AD,T

5100

25

32

35

12

30

12

16

6120

35

45

52

17

62

20

25

5440

17

25

42

12

35

12

9

10

WSC120AD,T

6800

27

37

65

17

75

20

14

17

8160

40

50

85

22

87

25

20

26

Notes:

1. Tested with standard filters. The WSC060AD,T has 25 mm (1 inch) standard fiters. The WSC072AD,T - 120AD,T has 50 mm (2 inch) standard filters. The difference in pressure drop

should be considered when utilizing optional 50 mm (2 inch) pleated filters.

2. OA = Outside Air and RA = Return Air

3. Nominal kW ratings at 380 V

Table PD-22a - Static Pressure Drops Through Accessories - (Inches of Water Column)

Econimizer with

Electric Heater

OA/RA Dampers

2

Accessory (kW)

3

Unit

Airflow

Standard

Pleated Filters

100% OA

100% RA

100% OA

100% RA

7-9

10-27

37-40

Model No.

(CFM)

Filters

1

50 mm (2 inch)

Downflow

Horizontal

1600

0.10

0.15

0.12

0.04

0.12

0.01

0.045

0.053

WSC060AD,T

2000

0.15

0.22

0.18

0.07

0.18

0.02

0.070

0.083

2400

0.22

0.29

0.26

0.10

0.26

0.04

0.100

0.120

1920

0.04

0.07

0.10

0.01

0.06

0.02

0.021

WSC072AD,T

2400

0.06

0.09

0.11

0.02

0.08

0.02

0.034

2880

0.09

0.12

0.13

0.04

0.10

0.04

0.052

2400

0.06

0.09

0.11

0.02

0.08

0.02

0.034

WSC090AD,T

3000

0.10

0.13

0.14

0.05

0.12

0.05

0.063

3600

0.14

0.18

0.21

0.07

0.25

0.08

0.102

3200

0.07

0.10

0.17

0.05

0.14

0.05

0.036

0.042

WSC120AD,T

4000

0.11

0.15

0.26

0.07

0.30

0.08

0.056

0.070

4800

0.16

0.20

0.34

0.09

0.35

0.10

0.081

0.106

Notes:

1. Tested with standard filters. The WSC060AD,T has 25 mm (1 inch) standard fiters. The WSC072AD,T - 120AD,T has 50 mm (2 inch) standard filters. The difference in pressure drop

should be considered when utilizing optional 50 mm (2 inch) pleated filters.

2. OA = Outside Air and RA = Return Air

3. Nominal kW ratings at 380 V

Table PD-23 — Electric Heater Voltage Correction

Factors (Apply to Auxiliary Heat
Capacity)

Nominal

Distribution

Capacity

Voltage

Voltage

Multipiler

200

200

1.00

380

0.84

415

400

0.93

415

1.00