beautypg.com

Temco dv5200 series – Temco Tool DV5200MB User Manual

Page 27

background image

27

Temco DV5200 Series

78674

Problem

Possible Cause

Solution

System Checks

(continued)

Pilot not lit.

Light pilot and wait for thermo-generator to heat up

sufficiently to power the main operator. If pilot fails

to light, or hold, refer to above sections.

Control knob not in ON

Rotate OFF/PILOT/ON control knob to the ON posi-

position.

tion.

Thermostat/wall switch

Thermostat not in ON position.

Turn thermostat ON, and adjust temperature control

will not cycle main

to call for heat.

burner.

Thermo-generator output

After the pilot has been lit for approximately three

voltage not within design

minutes, and only the thermo-generator wire con-

parameters.

nected to the main operator head, measure the

voltage acrossTPTH and TP. This open circuit volt-

age should be between 500mv and 750mv. Tune the

pilot adjustment screw until the mv reding falls with-

in these parameters. (Counterclockwise increases

mv reading, clockwise decreases) If unable to meet

minimum requirements, repalce thermo-generator.

Defective thermostat or

(A) With the pilot adjusted properly, ( After the pilot

thermostat wiring

has been lit for approximately three minutes, and

only the thermo-generator wire connected to the

main operator head, measure the voltage across

TPTH and TP. This open circuit voltage should be

between 500mv and 750mv. Tune the pilot adjust-

ment screw until the mv reading falls within these

parameters. Counterclockwise increases mv read-

ing, clockwise decreases), place a jumper wire be-

tween TPTH and TH. Take a mv reading across the

TPTH and TP terminals on the valve. This closed

circuit voltage should not fall below 300mv. Record

reading.

(B) Remove jumper wire form the TPTH and TH

connections, and reconnect the thermostat wires to

the same terminals. Take the closed circuit voltage

as described in the previous step. If the mv reading

drops below 150mvm, excessive resistance exists

in the thermostat circuit, and must be isolated and

eliminated.

Thermostat/wall switch

Defective wall switch.

Repeat the above troubleshooting items covered

will not cycle mian

under “Defective thermostat or thermostat wiring”,

burner.

except substitute the words “wall switch” where the

word “thermostat” appears in the instructions.

Excessive wire resistance.

Make certain that all mv connections are made us-

ing wire of the proper size. (Reference Page 23).

Valve wired wrong.

Thermo-generator leads must be connected to the

TPTH and TP connections of the main operator.

Thermostat wires must be connected to the TPTH ,

and TH terminals of the valve.