beautypg.com

Troubleshooting, Temco dv5200 series – Temco Tool DV5200MB User Manual

Page 25

background image

25

Temco DV5200 Series

78674

Troubleshooting

SIT Millivolt Valve

NOTE: Before troubleshooting the gas control system, be sure external shut off is in the “ON” position.

WARNING: Before doing any gas control service work, remove glass front!

Table 1

Valve Type

Main Operator

Safety Magnet

NOVA MV Plus

Minimum Voltage 145mV

Hold-in Current

Less than 285mA

Coil Resistance

2.25Ω ± 0.5Ω

Drop-out Current

Greater than 125mA

Coil Resistance

0.108Ω ± 0.003Ω

Problem

Possible Cause

Solution

Unit fails to operate

Batteries weak in remote unit

Replace batteries in both receiver and hand held

control

Pilot will not light.

Air in gas lines.

Bleed all air from gas lines.

Defective spill switch

Check for continuity across spill switch leads. Re-

place spill switch if excessive resistance is present,

or if circuit is electrically open.

Wrong inlet pressure.

With the main burner functioning, adjust the inlet

pressure regulator to supply gas to the appliance

within the design parameters of the appliance manu-

facturer. (Typically 7”NG, 11”LPG).

Defective spark electrode.

Replace piezo wire if insulation is cracked or the tip

is corroded.

Verify that the spark gap between the pilot and the

electrode is correct.

Defective piezo wire.

Replace piezo wire if insulation is damaged, or the

wire is broken or corroded.

Safety interlock function

Allow thermocouple to cool until the mv drops below

engaged.

the hold-in requirements of the safety magnet, (30

seconds or less). Re-light pilot.

Pilot will not hold.

Wrong inlet pressure.

With the main burner functioning, adjust the inlet

pressure regulator to supply gas to the appliance

within design parameters of the appliance manufac

turer. (Typically 7”NG, 11”LPG)

Pilot adjustment screw not

After the pilot has been lit for approximately three

properly adjusted.

minutes, and only the thermo-generator wire con-

nected to the main operator head, measure the volt-

age across TPTH and TP. This open circuit volt

age should be between 500mv and 750mv. Tune

the pilot adjustment screw until the mv reading

falls within these parameters. (Counter-clockwise

increases mv reading, clockwise decreases).

Thermocouple or

Make certain that the thermocouple and thermo-

thermo-generator not

generator are fully inserted and tightened into their

properly inserted into the pilot

receptacles in the pilot head. The thermocouple

housing

should be threaded into the valve hand-tight, plus

1/4 turn with wrench.

System Checks