beautypg.com

Temco dv5200 series – Temco Tool DV5200MB User Manual

Page 26

background image

26

Temco DV5200 Series

78674

Pilot will not hold

Thermocouple or

With the thermocouple and thermo-generator tips

thermo-generator has film

cool, clean the upper 3/8” with a very fine emery

continued...

build-up on tip.

cloth.

Electrical resistance too high.

Using a very fine emery cloth, clean thermo-genera-

tor and thermocouple connections at valve. Tighten

thermocouple into valve hand-tight, plus 1/4 turn

with a wrench.

Defective thermocouple.

Verify that thermocouple is not kinked or damaged.

(mv Plus systems)

Check open circuit voltage of thermocouple. Voltage

should be between 18mv and 28mv. If voltage is

less than 14mv, replace thermocouple.

Defective thermo-generator.

After the pilot has been lit for approximately three

(Millivolt system)

minutes, and only the thermo-generator wire con-

nected to the main operator head, measure the volt-

age across TPTH and TP. This open circuit voltage

should be between 500mv and 750mv. Tune the

pilot adjustment screw until the mv reading falls

within these parameters. (Counter-clockwise

increases mv reading, clockwise decreases)

Defective safety magnet.

Verify operation of safety magnet in the following

(mv Plus systems)

manner.

(A) Depress and hold pilot button.

(B) Verify open-circuit thermocouple voltage as de-

scribed in previous step.

(C) Reconnect thermocouple to valve.

(D) Measure the Millivoltage between the solder

button on the base of the safety magnet, and the

valve body. If the mv reading is above 6mv for

vented appliances, or 8.5 mv for un-vented

appliances, and the safety magnet does not hold,

replace the valve.

(E) If closed circuit mv reading is the same as the

open circuit reading, the coil is electrically open.

Replace the valve.

Defective Safety Magnet

Verify operation of safety magnet in the following

(Millivolt system)

manner.

(A) Remove all wires from the terminals of the main

operator.

(B) Measure the electrical voltage between the term-

inals TPTH and TP. If the voltage is above 110mV

and the safety magnet does not hold, replace the

valve.

Pilot orifice blocked.

Replace orifice with a new orifice of the exact size

and type.

Pilot drops out.

Wrong pilot orifice.

Replace the orifice with a new orifice supplied

specifically for the appliance and gas type in

question.

No gas to main burner

Low gas pressure to appliance. With the main burner functioning, adjust the inlet

pressure regulator to supply gas to the appliance

within the design parameters of the appliance manu-

facturer. (Typically 7”NG, 11”LPG).

Problem

Possible Cause

Solution

System Checks

(continued)