C:nxoptc1, Expander boards parameters slave address, Slave address – Nx Networks NX series User Manual
Page 79
Control keypad
79(86)
7
7.3.7
Expander board menu (M7)
The Expander board menu makes it possible for the user 1) to see what expander boards are
connected to the control board and 2) to reach and edit the parameters associated with the
expander board.
Enter the following menu level (G#) with the
right arrow menu button
At this level, the user can
browse through slots (see page 40) A to E with the
Browser buttons
to see what expander boards
are connected. The lowermost line of the display shows the number of parameters associated with
the board. It is possible to view and edit the parameter values in the same way as described in
chapter 7.3.2. See Table 7-9 and Figure 7-25.
Expander board parameters
Code
Parameter
Min
Max
Default
Cust
Selections
P7.1.1.1
AI1 mode
1
5
3
1=0…20 mA
2=4…20 mA
3=0…10 V
4=2…10 V
5=–10…+10 V
P7.1.1.2
AI2 mode
1
5
1
See P7.1.1.1
P7.1.1.3
AO1 mode
1
4
1
1=0…20 mA
2=4…20 mA
3=0…10 V
4=2…10 V
Table 7-9. Expander board parameters (board NXOPTA1)
Figure 7-25. Expander board information menu
G1
"
G5
READY
I/Oterm
C:NXOPTC1
READY
I/Oter m
G1
"
G2
READY
I/Oterm
READY
I/Oterm
enter
P1
"
P4
D:NXOPTC2
R EA DY
I/Oterm
G1
"
G2
R EA DY
I/Oterm
V1
"
V2
READY
I/Oter m
R EA DY
I/Oterm
Expander boards
Parameters
Slave address
126
CHANGE VALUE
CONFIRM CHANGE
Slave address
126
Baud rate
Auto
Monitor