Control keypad 61(86) – Nx Networks NX series User Manual
Page 61
Control keypad
61(86)
7
Fault
code
Fault
Possible cause
Correcting measures
16
Motor
overtemperature
Motor overheating has been detected by
frequency converter motor temperature
model. Motor is overloaded.
Decrease the motor load.
If no motor overload exists, check the
temperature model parameters.
17
Motor underload
Motor underload protection has tripped.
22
23
EEPROM
checksum fault
Parameter save fault
−
faulty
operation
−
component
failure
24
Changed data
warning
Changes may have occurred in the
different counter data due to mains
interruption
No special actions required. Take a
critical attitude to the counter data.
25
Microprocessor
watchdog fault
−
faulty
operation
−
component
failure
Reset the fault
and restart.
Should the fault re-occur, contact your
nearest distributor..
32
Fan cooling
Cooling fan of the frequency converter
does not start, when ON command is
given
Contact your nearest distributor..
34
CAN bus
communication
Sent message not acknowledged.
Ensure that there is another device on
the bus with the same configuration.
36
Control unit
NXS Control Unit can not control NXP
Power Unit and vice versa
Change control units
37
Device change
Option board changed.
Different power rating of drive.
Reset
38
Device added
Option board added.
Drive of different power rating added.
Reset
39
Device removed
Option board removed.
Drive removed.
Reset
40
Device unknown
Unknown option board or drive.
41
IGBT temperature
IGBT Inverter Bridge overtemperature
protection has detected too high a short
term overload current
Check loading.
Check motor size.
42
Brake resistor
overtemperature
Brake resistor overtemperature protection
has detected too heavy braking
Set the deceleration time longer.
Use external brake resistor.
43
Encoder fault
Note the exceptional Fault data record.
See 7.3.4.3. Additional codes:
1 = Encoder 1 channel A is missing
2 = Encoder 1 channel B is missing
3 = Both encoder 1 channels are missing
4 = Encoder reversed
Check encoder channel connections.
Check the encoder board.
50
Analogue input
I
in
< 4mA
(selected signal
range 4 to 20
mA)
Current at the analogue input is < 4mA.
−
control cable is broken or loose
−
signal source has failed
Check the current loop circuitry.
51
External fault
Digital input fault.
52
Keypad
communication
fault
The connection between the control
keypad and the frequency converter is
broken.
Check keypad connection and possible
keypad cable.
Table 7-3. Fault codes