5.2 Cooling

Enough free space should be left around the frequency converter to ensure sufficient air
circulation and cooling. The required dimensions for free space are in the table below.

If several units are mounted above each other the required free space equals C + D (see figure
below). Moreover, the outlet air used for cooling by the lower unit must be directed away from the
inlet air to be used by the upper unit.

Type

Dimensions

A

A

2

B

C

D

0003—0012 NX_5

20

20

100

50

0016—0031 NX_5

20

20

120

60

0038—0061 NX_5

30

20

160

80

0072—0105 NX_5

80

80

300

100

0140—0205 NX_5

20

200

(150*)

80

300

200

Table 5-6. Mounting space dimensions

Figure 5-6. Installation space

Type

Cooling air required [m

3

/h)

0004—0015 NX_2
0003—0012 NX_5
0005—0019 NX_6

70

0018—0032 NX_2
0016—0031 NX_5
0022—0062 NX_6

190

0048—0078 NX_2
0038—0061 NX_5

0085 NX_6

425

0092—0150 NX_2
0072—0105 NX_5

425

0140—0205 NX_5
0100—0122 NX_6

650

Table 5-7. Required cooling air.

A

= clearance around the freq. converter (see also A

2

and B)

A

2

= clearance needed on either side of the frequency converter

for fan change (without disconneting the motor cables)

*

= min. clearance for fan change (without disconnecting the

motor cables) between two frequency converters

B

= distance from one frequency converter to another or

distance to cabinet wall

C

= free space above the frequency converter

D

= free space underneath the frequency converter