16(86) technical data, 2 power ratings, Motor shaft power – Nx Networks NX series User Manual
Page 16
16(86)
Technical data
4
4.2 Power
ratings
4.2.1
NX5 – Mains voltage 380—500 V
High overload = 200% starting torque, 2 sec/20 sec, 150% overloadability, 1 min/10 min
Low overload = 150% starting torque, 2 sec/20 sec, 110% overloadability, 1 min/10 min
All sizes up to and including FR8 available with IP21 enclosure and IP54 as option.
Table 4-1. Power ratings and dimensions of the NX, supply voltage 380—500V.
Mains voltage 380-500 V, 50/60 Hz, 3~
Frequency
converter
type
10%
overload
50%
overload
10%
overload
50%
overload
40 deg C
50 deg C
40 deg C
50 deg C
P (kW)
P (kW)
P (kW)
P (kW)
NXS 0003
3,1
3,5
2,2
3,5
1,1
0,75
1,5
1,1
FR4/IP21, IP54
128x292x190
5
NXS 0004
4,0
4,4
3,1
4,4
1,5
1,1
2,2
1,5
FR4/IP21, IP54
128x292x190
5
NXS 0005
5,4
6
4
6
2,2
1,5
3
2,2
FR4/IP21, IP54
128x292x190
5
NXS 0007
7
7,7
5,4
7,7
3
2,2
4
3
FR4/IP21, IP54
128x292x190
5
NXS 0009
9
10
7
10
4
3
5,5
4
FR4/IP21, IP54
128x292x190
5
NXS 0012
12
13,2
9
13,2
5,5
4
7,5
5,5
FR4/IP21, IP54
128x292x190
5
NXS 0016
16
18
12
18
7,5
5,5
11
7,5
FR5/IP21, IP54
144x391x214
8,1
NXS 0022
22
24
16
24
11
7,5
15
11
FR5/IP21, IP54
144x391x214
8,1
NXS 0031
31
35
22
35
15
11
18,5
15
FR5/IP21, IP54
144x391x214
8,1
NXS 0038
38
47
31
47
18,5
15
22
18,5
FR6/IP21, IP54
195x519x237
18,5
NXS 0045
45
54
38
54
22
18,5
30
22
FR6/IP21, IP54
195x519x237
18,5
NXS 0061
61
68
45
68
30
22
37
30
FR6/IP21, IP54
195x519x237
18,5
NXS 0072
72
92
61
92
37
30
45
37
FR7/IP21, IP54
237x591x257
35
NXS 0087
87
108
72
108
45
37
55
45
FR7/IP21, IP54
237x591x257
35
NXS 0105
105
131
87
131
55
45
75
55
FR7/IP21, IP54
237x591x257
35
NXS 0140
140
158
105
158
75
55
90
75
FR8/IP21, IP54
285x721x288
58
NXS 0168
168
210
140
210
90
75
110
90
FR8/IP21, IP54
285x721x288
58
NXS 0205
205
252
168
252
110
90
132
110
FR8/IP21, IP54
285x721x288
58
High
Dimensions
WxHxD
Weight
10%
overload
current
(A)
Rated
continuous
current I
L
(A)
Motor shaft power
Mechanical size
Enclosure and
protection class
Rated
Continuous
current I
H
(A)
50%
overload
current
(A)
380V supply
500V supply
Loadability
Low