beautypg.com

Nx Networks NX series User Manual

Page 32

background image

32(86)

Cabling and connections

6

6.1.2

Installation instructions

1

Before starting the installation, check that none of the components of the
frequency converter are live.

2

If the frequency converter is installed outside either a switchgear,
separate cubicle or electrical room, it must be equipped with a protection
cover (see e.g. Figure 6-4) as provided by the regulations for IP21
protection class. For installations in a switchgear, separate cubicle or
electrical room, the cable protection plate is normally not necessary.

3

Place the motor cables sufficiently far from other cables:

!

Avoid placing the motor cables in long parallel lines with other
cables

!

If the motor cables runs in parallel with other cables, note the

minimum distances between the motor cables and other cables
given in the table below.

!

The given distances also apply between the motor cables and

signal cables of other systems.

!

The maximum length of the motor cables is 300 m (level H,
units with power greater than 1.5 kW) and 100 m (units with power
from 0.75 to 1.5 kW).

!

The

motor cables should cross other cables at an angle of 90

degrees.

4

If cable insulation checks are needed, see Chapter 6.1.4.

Distance

between cables

[m]

Shielded

cable

[m]

0.3

50

1.0

200

Continues on the next page