Grounding lug, Procedure – Paradyne IP DSLAM GranDSLAM 4200 User Manual

Page 39

background image

2. Cabling

4200-A2-GN20-40

January 2004

2-15

Grounding Lug

Procedure

To connect the unit to a ground:

1. Strip back the insulation approximately 5/16 of an inch (8 mm) on 14 AWG

copper ground wire.

2. Loosen the screw on the grounding lug located on the side panel near the

front of the unit.

3. Insert the stripped end of the wire through the bottom of the grounding lug and

tighten the screw. Ensure that the screw makes contact with the stripped
portion of the wire.

4. Attach the ground wire to an earth ground.