beautypg.com

Powerware 9395 UPS and Plus 1 UPS 650825 kVA User Manual

Page 38

background image

UPS INSTALLATION PLAN AND UNPACKING

EATON Powerware

®

9395 UPS (650–825 kVA) Installation and Operation Manual

S 164201725 Rev 2 www.powerware.com

3−16

Table 3-13. Power Cable Conduit Requirements (continued)

Number of

Conduits

Minimum Conduit

Trade Size

Number of Wires

in Conduit

Terminal

Voltage

UPS Model

Powerware 9395−825/825

400 Vac

AC Input to UPS Rectifier

(A, B, C, Ground)

4

3

5

AC Input to UPS Rectifier (Separate Feed)

(A, B, C, Ground)

4

2

3

(Each UPM)

AC Input to Bypass and Output (Four Wire)

(A, B, C, Ground)

4

3

4

AC Input to Bypass and Output (Five Wire)

(A, B, C, Neutral, Ground)

5

3

5

480 Vac

AC Input to UPS Rectifier

(A, B, C, Ground)

4

3

4

AC Input to UPS Rectifier (Separate Feed)

(A, B, C, Ground)

4

2

2

(Each UPM)

AC Input to Bypass and Output (Four Wire)

(A, B, C, Ground)

4

3

4

AC Input to Bypass and Output (Five Wire)

(A, B, C, Neutral, Ground)

5

3

5

DC

Battery

(Positive, Negative, Ground)

See Note

NOTE Select conduit taking into consideration the DC input wire sizes listed in Table 3-4 on page 3−9 or Table 3-5 on page 3−10, the DC terminations
listed in Table 3-9 on page 3−13, type of battery installation, and requirements from NEC Table 4, Electrical Metallic Tubing (EMT).

External overcurrent protection and disconnect are not provided by this product, but
are required by codes. Refer to Table 3-4 on page 3−9, Table 3-5 on page 3−10, or
Table 3-6 on page 3−11 for wiring requirements. If an output lockable disconnect is
required, it is to be supplied by the customer.

Table 3-14 lists the recommended rating for input circuit breakers.

Table 3-15 lists the recommended rating for input circuit breakers with separate
rectifier inputs UPS. A separate breaker is required for each UPM.

Table 3-14. Recommended Input Circuit Breaker Ratings

UPS Model

Input Rating

Load Rating

400V

480V

Powerware 9395−825/650

80% Rated

1600A

1200A

100% Rated

1200A

1000A

Powerware 9395−825/750

80% Rated

1600A

1600A

100% Rated

1600A

1200A

Powerware 9395−825/825

80% Rated

2000A

1600A

100% Rated

1600A

1200A