beautypg.com

Powerware 9395 UPS and Plus 1 UPS 650825 kVA User Manual

Page 132

background image

UNDERSTANDING UPS OPERATION

EATON Powerware

®

9395 UPS (650–825 kVA) Installation and Operation Manual

S 164201725 Rev 2 www.powerware.com

6−20

MAINTENANCE
BYPASS PANEL

Output

from

UPS

MIS

To UPS

Rectifier

Input

RIB:

Rectifier Input Breaker

BIB:

Bypass Input Breaker

MIS:

Maintenance Isolation Breaker

MBP:

Maintenance Bypass Breaker

MBP

Backfeed
Contactor

K5

K3

AC Input

Battery

Breaker

BATTERY SYSTEM

UPS

CRITICAL LOAD

DISTRIBUTION UNIT

NOTE If installing a maintenance bypass, a minimum of two separate feeds with upstream feeder breakers, or a single feed with two
upstream feeder breakers, must be provided: one for the UPS or rectifier input breaker (RIB) (if installed) and one for the maintenance bypass
input. DO NOT use a single feed or a single feeder breaker to supply both the UPS or RIB and the maintenance bypass. If a bypass input
breaker (BIB) is installed in the maintenance bypass and a single−feed UPS is being installed, a single feed to the maintenance bypass is
acceptable for supplying both the UPS and the bypass.

Static

Switch

(Provided by Others)

Output

Contactor

AC Input

RIB

BIB

To UPS
Bypass

Input

Figure 6-17. Simplified Dual−Feed UPS with Maintenance Bypass Panel