UPS INSTALLATION PLAN AND UNPACKING

EATON Powerware

®

9395 UPS (650–825 kVA) Installation and Operation Manual

S 164201725 Rev 2 www.powerware.com

3−10

Table 3-5. Input/Output Ratings and External Wiring Requirements for the Powerware 9395−825/650, 9395−825/750, and 9395−825/825
– Separate Battery

Basic Unit Rating

Units

Rating 50/60 Hz

kVA

kW

650
585

650
591

750
675

750
682

825
742

825
750

Input and Output Voltage

Volts

400/400

480/480

400/400

480/480

400/400

480/480

AC Input to UPS Rectifier (0.98 Minimum pF)

Full load current plus battery recharge current
(3) Phases, (1) Ground

A

Amps

1079

891

1245

1028

1369

1130

Minimum Conductor Size
Number per Phase

AWG or kcmil

(each)

500

(4)

500

(3)

500

(4)

500

(4)

500

(5)

500

(4)

AC Input to UPS Bypass (Four Wire)

Full Load Current
(3) Phases, (1) Ground

B

Amps

938

782

1083

902

1191

992

Minimum Conductor Size
Number per Phase

AWG or kcmil

(each)

500

(3)

350

(3)

500

(4)

500

(3)

500

(4)

500

(4)

AC Input to UPS Bypass (Five Wire)

Full Load Current
(3) Phases, (1) Neutral, (1) Ground

B

Amps

938

782

1083

902

1191

992

Minimum Conductor Size
Number per Phase

AWG or kcmil

(each)

400

(4)

500

(3)

500

(5)

500

(4)

500

(5)

500

(5)

DC Input from Each Battery Disconnect to Each UPS
UPM

(1) Positive, (1) Negative

C

Amps per UPM

551

551

551

551

551

551

Minimum Conductor Size
Number per Pole

AWG or kcmil

(each)

250

(3)

250

(3)

250

(3)

250

(3)

250

(3)

250

(3)

AC Output to Critical Load (Four Wire)

Full Load Current
(3) Phases, (1) Ground

D

Amps

938

782

1083

902

1191

992

Minimum Conductor Size
Number per Phase

AWG or kcmil

(each)

500

(3)

350

(3)

500

(4)

500

(3)

500

(4)

500

(4)

AC Output to Critical Load (Five Wire)

Full Load Current
(3) Phases, (1) Neutral, (1) Ground

D

Amps

938

782

1083

902

1191

992

Minimum Conductor Size
Number per Phase

AWG or kcmil

(each)

400

(4)

350

(3)

500

(5)

500

(3)

500

(5)

500

(4)

Neutral Bonding Jumper (Four Wire Output Only)

Minimum Conductor Size
Number

AWG or kcmil

(each)

4/0

(1)

4/0

(1)

4/0

(1)

4/0

(1)

4/0

(1)

4/0

(1)

NOTE Callout letter

A

,maps to Figure 6-6, Figure 6-8, Figure 6-10, or Figure 6-12 starting on page 6−9. Callout letters

B

,

C

, and

D

map to Figure 6-6,

Figure 6-8, Figure 6-10, Figure 6-12, Figure 6-13, Figure 6-14, Figure 6-15, or Figure 6-16 starting on page 6−9.