UPS OPERATING INSTRUCTIONS

EATON Powerware

®

9395 UPS (650–825 kVA) Installation and Operation Manual

S 164201725 Rev 2 www.powerware.com

7−23

20. Repeat Steps 8 through 19 for each UPS in the distributed bypass system.

NOTE To transfer to Normal mode after starting individual UPMs, follow the procedure in paragraph 7.4.5 .

7.4.4

Transfer from Normal to Bypass Mode

To transfer the critical load to Bypass mode:

C

A

U

T

I

O

N

In Bypass mode, the critical load is not protected from commercial power interruptions and abnormalities.

1.

On any UPS, press the

CONTROLS

pushbutton on the main menu bar. The System

Status screen is displayed.

2.

On the System Status screen, select the

BYPASS

command.

3.

Press the

CONTROLS

pushbutton on the System Status menu bar. The Bypass

Control Command screen is displayed.

4.

On the Bypass Control Command screen, select

GO TO BYPASS

.

5.

Press the

SELECT

pushbutton on the Bypass Command menu bar.

All of the UPSs transfer to Bypass mode and the critical load is immediately
supplied by the bypass source from all UPSs. If the bypass source is not
available, the power module remains on and an alarm sounds.

The

BYPASS

status indicator is illuminated. The Bypass status indicates

ON. The

UPM status indicates

READY. The power module remains on.

W

A

R

N

I

N

G

Power is present inside the UPS cabinet sections.

7.4.5

Transfer from Bypass to Normal Mode

To transfer the critical load to Normal mode:

1.

If not already closed, close the battery breaker.

2.

On any UPS, press the

CONTROLS

pushbutton on the main menu bar. The System

Status screen is displayed.

3.

On the System Status screen, select the

UPS

command.

4.

Press the

CONTROLS

pushbutton on the System Status menu bar. The UPS

Control Command screen is displayed.

5.

On the UPS Control Command screen, select

GO TO NORMAL

.

6.

Press the

SELECT

pushbutton on the UPS Command menu bar.

All of the UPSs transfer to Normal mode. If the power module is not available,
the system remains on bypass and an alarm sounds.

The

NORMAL

status indicator is illuminated. The UPS status indicates

ONLINE.

The UPM status indicates

ONLINE.