UPS INSTALLATION PLAN AND UNPACKING
EATON Powerware
®
9395 UPS (650–825 kVA) Installation and Operation Manual
S 164201725 Rev 2 www.powerware.com
3−11
AC input to the UPS with separate rectifier inputs is wired as if each UPM is rated for
275 kVA (see Table 3-6). The bypass input, battery input, and output are wired the
same as a separate battery UPS (see Table 3-5).
Table 3-6. Separate Rectifier Input UPM Ratings and External Wiring Requirements for the
Powerware 9395−825/650, 9395−825/750, and 9395−825/825 – Separate Battery
Basic UPM Rating
Units
Rating 50/60 Hz
kVA
kW
275
247.5
275
250
Input Voltage
Volts
400
480
AC Input to each UPM Rectifier (0.98 Min. pF)
Full load current plus battery recharge current
(3) Phases, (1) Ground
A
Amps
456
370
Minimum Conductor Size
Number per Phase
AWG or kcmil
(each)
2/0
(3)
4/0
(2)
NOTE Callout letter
A
, maps to Figure 6-13 through Figure 6-16 starting on page 6−16.