UPS INSTALLATION PLAN AND UNPACKING

EATON Powerware

®

9395 UPS (650–825 kVA) Installation and Operation Manual

S 164201725 Rev 2 www.powerware.com

3−11

AC input to the UPS with separate rectifier inputs is wired as if each UPM is rated for
275 kVA (see Table 3-6). The bypass input, battery input, and output are wired the
same as a separate battery UPS (see Table 3-5).

Table 3-6. Separate Rectifier Input UPM Ratings and External Wiring Requirements for the
Powerware 9395−825/650, 9395−825/750, and 9395−825/825 – Separate Battery

Basic UPM Rating

Units

Rating 50/60 Hz

kVA

kW

275

247.5

275
250

Input Voltage

Volts

400

480

AC Input to each UPM Rectifier (0.98 Min. pF)

Full load current plus battery recharge current
(3) Phases, (1) Ground

A

Amps

456

370

Minimum Conductor Size
Number per Phase

AWG or kcmil

(each)

2/0

(3)

4/0

(2)

NOTE Callout letter

A

, maps to Figure 6-13 through Figure 6-16 starting on page 6−16.