Isolated Alarm Relay Interface

The isolated alarm relay interface uses a 15-pin, male, 42D-sub
connector.

1

2

3

4

5

6

7

8

9

10

11 12

13 14 15

Figure 21. 15-Pin Serial Port

Relay Interface of Powerware 9150

Pin No. Connection

System State

Utility Failure

1 - 2 Closed
1 - 3 Closed

Line normal
Line failure

Low Battery

4 - 5 Closed
4 - 6 Closed

Battery normal
Battery low

UPS on Bypass

10 - 11 Closed
10 - 12 Closed

On UPS
On Bypass

UPS On or
UPS Alarm

7 - 9 Closed
7 - 8 Closed

UPS on
UPS alarm

UPS Shutdown
(in Battery Mode only)

13 - 15 Closed

UPS shutdown when operating in Battery Mode. UPS can be shut down
by sending a hi-level signal (+5V to +15V) to Pin 15(+) and 14(-), or by
connecting Pin 15 to Pin 13. This signal must be present for a minimum
of 5 seconds.

NOTE The relay contacts are rated for a maximum 1A/30 Vac or 0.2A/60 Vdc. All
relay outputs are isolated from the other circuits of the UPS. The relay contacts must
not be connected to any utility connected circuits. Reinforced insulation to the utility is
required.