UPS Shutdown

To shut down the UPS:

1. Remove the front panel. Lift from the bottom of the panel and

then pull out (see Figure 17).

2. Turn the Maintenance Bypass switch to the SERVICE or BYPASS

position.

3. Turn off the UPS ON/OFF switch (the

position).

4. Turn the UPS battery circuit breaker CB1 and optional CB2 to

the OFF position.

The UPS stops supplying power and is disconnected internally
from the batteries. The load is powered by the utility.