beautypg.com

Powerware 9150 User Manual

Page 49

background image

Operation

45

Powerware

®

9150 User’s Guide

:

www.powerware.com

W A R N I N G

: If the input frequency is not correct and the UPS is not synchronized to utility

power (LINE ON indicator is off), the use of the Maintenance Bypass switch causes
a break in the output voltage. Wait until the LINE ON indicator illuminates before
using the switch.

: Do not use the Maintenance Bypass switch if the UPS is configured as a frequency

converter (50 Hz in/60 Hz out or 60 Hz in/50 Hz out); it could cause damage to the
load.

To operate the Maintenance Bypass switch:

1. Check to ensure the LINE ON indicator is on.

2. Turn the Maintenance Bypass switch through the SERVICE

position to the BYPASS position. The UPS is now bypassed,
with the load powered from utility.

To return to Normal Mode:

1. Turn the Maintenance Bypass switch to the SERVICE position.

2. Turn on the UPS ON/OFF switch (the

|

position). If the switch

is already in this position, turn it off and then on again.

C A U T I O N

Before turning the Maintenance Bypass switch to the UPS position, verify that the UPS
ON, LINE ON, and LOAD indicators are on. This may take three to four minutes.

3. Turn the Maintenance Bypass switch to the UPS position to

return to Normal Mode. The UPS is powering the load.