beautypg.com

Precision Trading 60 R3.0 User Manual

Page 50

background image

Operator Manual, Supercharger 60

R3.0

Page 50 of 62

Figure 10 - Voltage Control Board Adjustments

9.2.5.2. VOLTAGE CONTROL - See [Figure 10]

9.2.5.2.1.

R11, FLOAT VOLTAGE:

• Connect a CAL-100 Calibrator or a power supply

capable of producing at least 10V (very little current
required) to the CAL (-) and CAL (COMMON) test
points. The positive lead to COMMON and the
negative lead to CAL (-).

• Set the calibrator/power supply to 2.70V to simulate

a battery that has 27.0V.

NOTE: The Calibrator voltage is 1/10 of the
simulated battery voltage.

• Connect a battery to the Charger-Analyzer.
• Set the Voltage Control Mode Switch to CV

(Constant Voltage)

• Program for 10A of Topping current.
• Enter 24 in the cell selector (nominal battery

voltage).

• Start the Charger-Analyzer in Single rate. The

current will rise to the programmed 10A.

• Increase the power supply voltage towards 2.8V and

observe the current.

• The charging current will begin to decrease at about

2.75V and should reach zero as the voltage is
advanced to 2.8V.

NOTE: Ignore the actual battery voltage. The Float

voltage control circuit is responding to the simulated
battery voltage as provided by the power supply
.