Precision Trading 60 R3.0 User Manual
Page 39

Operator Manual, Supercharger 60
R3.0
Page 39 of 62
8.9 FULL DISCHARGE.
8.9.1. Settings:
8.9.1.1. Set the Current selectors to zero.
8.9.1.2. Set the Time selectors to 1/01.
8.9.1.3. Set the Cell selector to 20.
8.9.2. Start the unit in the full discharge mode (red). Unit will run. Increase the
discharge current selector to any value above 1 AMP (010). Unit will continue to
run.
8.9.3. Switch to Auto discharge. Unit will go to Capacity Failure. Disconnect from the
voltage source. Reset.
8.10 CURRENT TRACKING.
8.10.1. Settings:
8.10.1.1. Set the Time selectors to 1/01 and the Cell selector consistent with the
battery.
8.10.1.2. Set the main charge current selector to 25 AMPS (250)
8.10.1.3. Set the topping charge current selector to 1 AMP (010).
8.10.2. Connect the Battery Cable to the battery.
8.10.3. Start the unit in the two rate mode. Current will rise to 25.0A ±0.35A.
8.10.4. Switch to the single rate mode. Current will drop to 1.0A ±0.2A. Reset.
8.10.5. Repeat this test for other high and low settings.
8.10.6. Repeat also for the discharge mode.
8.10.7. NOTE: In discharge, the readings may be lower by 0.1A to 0.2A.
8.10.8. See 8.2.4 for adjustments
8.11 VOLTAGE CONTROL.
8.11.1. See 8.2.7 for adjustments.