beautypg.com

Chapter 10 troubleshooting, Typical alarms and conditions – Powerware 9355 User Manual

Page 59

background image

EATON Powerware

®

9355 Parallel UPS (10/15 kVA) User’s Guide

S 164201601 Rev A www.powerware.com

53

Chapter 10

Troubleshooting

The Powerware 9355 is designed for durable, automatic operation and
also alerts you whenever potential operating problems may occur.
Usually the alarms shown by the control panel do not mean that the
output power is affected. Instead, they are preventive alarms intended
to alert the user. Use the following troubleshooting chart to determine
the UPS alarm condition.

Typical Alarms and Conditions

The following table describes typical alarms and conditions; check the
Event Log through the control panel for a list of active alarms. If an alarm
appears with a service code, please contact the Help Desk (see
page 56).

Alarm or Condition

Possible Cause

Action

On Battery

LED is on.
1 beep every second.

A utility failure has occurred and the
UPS is in Battery mode.

The UPS is powering the equipment with battery
power. Prepare your equipment for shutdown.

Battery Low

LED is on.
Continuous beep for
10 seconds.

The battery is running low.

Five minutes or less of battery power remains
(depending on load configuration and battery
charge). Save your work and turn off your
equipment.
When utility power is restored, the UPS restarts
automatically, provides power to the load, and
charges the battery.

Battery Breaker

LED is on.
1 beep every second.

The UPS does not recognize the
internal batteries.

Verify the battery circuit breaker is in the ON
position. If the condition persists, contact your
service representative.

Overload

LED is on.
1 beep every second.

Power requirements exceed the UPS
capacity (greater than 100% of
nominal).

Remove some of the equipment from the UPS. The
UPS continues to operate, but may switch to
Bypass mode if the load increases. The alarm
resets when the condition becomes inactive.