PARALLEL INSTALLATION

EATON Powerware

®

9355 Parallel UPS (10/15 kVA) User’s Guide

S 164201601 Rev A www.powerware.com

21

13. Hardwire the UPS input terminations.

See Table 1 for specifications and Figure 15 for a detailed view of
the UPS terminal block.

NOTE Input neutral must be wired for proper operation. Failure to connect an input neutral
will void the warranty.

NOTE The Powerware 9355 UPS is a single-feed UPS only.

Table 1. UPS Terminal Block Wiring

10 kVA

Input Voltage

Wire

Function

Input Circuit

Breaker Size

L1, L2, L3, N

Wire Size

1

Ground

Wire Size

1

Tightening

Torque

Conduit Size

2, 3

(Number of Conduits)

208

Input

45A

6 AWG

10 AWG

120 lb in

1 00”

d i (1)

220

p

45A

8 AWG

10 AWG

120 lb in

(13.5 Nm)

1.00” conduit (1)

208

Output

8 AWG

10 AWG

120 lb in

1 00”

d i (1)

220

p

8 AWG

10 AWG

120 lb in

(13.5 Nm)

1.00” conduit (1)

15 kVA

Input Voltage

Wire

Function

Input Circuit

Breaker Size

L1, L2, L3, N

Wire Size

1

Ground

Wire Size

1

Tightening

Torque

Conduit Size

2, 3

(Number of Conduits)

208

Input

60A

4 AWG

10 AWG

120 lb in

1.25” conduit (1)

220

p

60A

4 AWG

10 AWG

120 lb in

(13.5 Nm)

1.25” conduit (1)

208

Output

6 AWG

10 AWG

120 lb in

1 00”

d i (1)

220

p

6 AWG

10 AWG

120 lb in

(13.5 Nm)

1.00” conduit (1)

1

Use only 90°C-rated copper wire. Minimum wire size is based on 120/208 full load ratings applied to NEC Code

Table 310-16. Code may require a larger AWG size than shown in this table because of temperature, number of
conductors in the conduit, or long service runs. Wire lengths should be the same size. Follow local requirements.

2

Per NEC article 300-20(a), all three-phase conductors must be run in the same conduit. Neutral and ground must be

run in the same conduit as the phase conductors.

3

Conduit is sized to accommodate one neutral conductor the same size as the phase conductor and one #8 AWG

ground conductor. If two neutral conductors or an oversized neutral conductor are to be installed, check the size of the
conduit needed to accommodate the extra wire or size and use that conduit size in place of the conduit size listed.
Conduit sizes were chosen from NEC Table C1, type letters RHH, RHW, RHW-2, TW, THW, THHW, THW-2.