Powerware 9355 User Manual
Page 51
OPERATION
EATON Powerware
®
9355 Parallel UPS (10/15 kVA) User’s Guide
S 164201601 Rev A www.powerware.com
45
Table 3. User Settings (continued)
Default Setting
Available Settings
Description
Start Screen
Eaton Powerware logo
Mimic screen
Eaton Powerware logo
User Password
Enabled/Disabled
If Enabled is selected, the password is USER.
Disabled
Audible Alarms
Normal Sound/Disabled
Normal Sound
Battery Charging
ABM cycling/constant
ABM cycling
Automatic Battery Tests
Enabled/Disabled
Enabled automatically runs the battery test
once a month.
Enabled
Full Power Battery Test
Enabled/Disabled
Enabled
Number of Battery Strings
0 through 22
(see “Configuring the UPS for EBMs” on
page 47)
2 strings for UPS-32 models
4 strings for UPS-64 models
Battery Capacity
1 through 65535 watts per cell
34 W/cell
Battery Low Alarm Level
1.750 through 1.950 volts per cell
1.880 V/cell
Bypass Voltage High Limit
+1 through +20% (1% increments)
120V +10%
Bypass Voltage Low Limit
-1 through -20% (1% increments)
120V -15%
Nominal Output Frequency
50 Hz or 60 Hz
60 Hz
Synchronization
Enabled/Disabled
Enabled
Synchronization Window
±0.5 through ±3.0 Hz
(0.1 Hz increments)
±2.0 Hz
Unsynchronized Transfer to Bypass
Allowed/Not Allowed
Not Allowed
Output Frequency Slew Rate
0.1 though 5 hertz per second
(0.1 Hz increments)
0.5 Hz/s
Usage of Bypass
Enabled/Disabled
Enabled
Transfer to Bypass When Overload
After a delay/Immediately
After a delay
Automatic Start Delay
-1 through 32767 seconds
(-1 means disabled)
0s
Control Commands from X-Slot1
Allowed/Disabled
Allowed
Control Commands from X-Slot2/Serv
Allowed/Disabled
Allowed