OPERATION

EATON Powerware

®

9355 Parallel UPS (10/15 kVA) User’s Guide

S 164201601 Rev A www.powerware.com

45

Table 3. User Settings (continued)

Default Setting

Available Settings

Description

Start Screen

Eaton Powerware logo
Mimic screen

Eaton Powerware logo

User Password

Enabled/Disabled
If Enabled is selected, the password is USER.

Disabled

Audible Alarms

Normal Sound/Disabled

Normal Sound

Battery Charging

ABM cycling/constant

ABM cycling

Automatic Battery Tests

Enabled/Disabled
Enabled automatically runs the battery test
once a month.

Enabled

Full Power Battery Test

Enabled/Disabled

Enabled

Number of Battery Strings

0 through 22
(see “Configuring the UPS for EBMs” on
page 47)

2 strings for UPS-32 models
4 strings for UPS-64 models

Battery Capacity

1 through 65535 watts per cell

34 W/cell

Battery Low Alarm Level

1.750 through 1.950 volts per cell

1.880 V/cell

Bypass Voltage High Limit

+1 through +20% (1% increments)

120V +10%

Bypass Voltage Low Limit

-1 through -20% (1% increments)

120V -15%

Nominal Output Frequency

50 Hz or 60 Hz

60 Hz

Synchronization

Enabled/Disabled

Enabled

Synchronization Window

±0.5 through ±3.0 Hz
(0.1 Hz increments)

±2.0 Hz

Unsynchronized Transfer to Bypass

Allowed/Not Allowed

Not Allowed

Output Frequency Slew Rate

0.1 though 5 hertz per second
(0.1 Hz increments)

0.5 Hz/s

Usage of Bypass

Enabled/Disabled

Enabled

Transfer to Bypass When Overload

After a delay/Immediately

After a delay

Automatic Start Delay

-1 through 32767 seconds
(-1 means disabled)

0s

Control Commands from X-Slot1

Allowed/Disabled

Allowed

Control Commands from X-Slot2/Serv

Allowed/Disabled

Allowed