42
The following table shows the indicator status and description.
Indicator
Status
Description
On
The UPS is operating normally.
Green
Flashing
S The UPS is starting up or is shut down and waiting for power to return.
S A new information message is active.
S Bypass is not available.
Off
The UPS is turned off and will not turn on automatically.
Yellow
On
The UPS is in Battery mode.
Yellow
On
The UPS is in Bypass mode.
On
The UPS has an active alarm.
Red
Flashing
There is a new UPS alarm condition. See “Troubleshooting” on page 53 for
additional information.
Changing the Language
Press and hold the first button on the left for approximately five seconds
to select the language menu. This action is possible from any LCD menu
screen.
Display Functions
As the default or after 15 minutes of inactivity, the LCD displays the
selectable startup screen. The default is the Eaton Powerware logo and
can be changed to the Mimic screen in the User Settings menu.
The backlit LCD automatically dims after a long period of inactivity. Press
any button to restore the screen.
Use the two middle buttons ( and ) to scroll through the menu
structure. Press the
button to enter a submenu. Press the
button
to select an option. Press the
ESC
button to cancel or return to the
previous menu.