Powerware hot sync can bridge card – Powerware 9355 User Manual
Page 34
INSTALLING OPTIONS
EATON Powerware
®
9355 Parallel UPS (10/15 kVA) User’s Guide
S 164201601 Rev A www.powerware.com
28
Powerware Hot Sync CAN Bridge Card
The Powerware Hot Sync CAN Bridge Card, shown in Figure 22, can be
installed to provide connectivity for operational mode control and
metering of a parallel system at any UPS in the system.
Plug-In Terminal Block
Figure 22. Powerware Hot Sync CAN Bridge Card
To install the Powerware Hot Sync CAN Bridge Card:
1.
Remove the front covers of all cabinets, starting with the top
cabinet.
Press and release the handle latch at the bottom of each cover and
then lift the cover up and off the cabinet (see Figure 23).
Figure 23. Removing the Front Covers