UPS SETUP

EATON Powerware

®

9355 Parallel UPS (10/15 kVA) User’s Guide

S 164201601 Rev A www.powerware.com

8

Floor Loading

When planning the installation, consider the UPS weight for floor
loading. The strength of the installation surface must be adequate for
point and distributed loadings. The approximate weights are shown in
the following table.

Standard Model Floor Loadings (2-High/3-High Cabinets)

Powerware 9355

Maximum

Weight

Point Loading

lb/in

2

(kg/cm

2

)

2-High UPS

381 lb (173 kg)

95 (6.7)

3-High UPS-32

587 lb (266 kg)

147 (10.3)

3-High UPS-64

619 lb (281 kg)

155 (10.9)

2-High EBM

480 lb (218 kg)

120 (8.4)

3-High EBM

710 lb (322 kg)

178 (12.5)

Clearances

The following clearances are recommended for the Powerware 9355
UPS:

From Front of Cabinet

36” (91.4 cm) working space

From Back of Cabinet

6” (15.2 cm)