OPERATION

EATON Powerware

®

9355 Parallel UPS (10/15 kVA) User’s Guide

S 164201601 Rev A www.powerware.com

44

User Settings

The following table displays the options that can be changed by the
user.

NOTE Changes to the output voltage or frequency options should be made before turning
on the UPS; otherwise, the changes do not take effect.

Table 3. User Settings

Description

Available Settings

Default Setting

Set Date and Time

Set Month
Date: mm/dd/yyyy
Time: 24:00

01/01/2003
00:00

Display Contrast

Adjust contrast with up/down arrow buttons

Moderate

Change Language

Select Language:
Elegir idioma

English

Set NominalOutput Voltage

Output:
[120V/208V] [127V/220V]

120V/208V

Relay Config

Relay: [Alarm 1] [X-Slot 1-1/2/3/4] or
[X-Slot 2-1/2/3/4]
Setup: [Battery Low] [On Battery] [On
Bypass] [UPS ok] [custom] [empty]

Alarm 1: empty
X-Slots (1 or 2)
#1: UPS ok
#2: On Bypass
#3: Summary Alarm
#4: On Battery

Signal Inputs

[empty] [Logic]
Signal Input must be wired to the CAN Bridge
Card (see Figure 24 on page 30).
For more information, refer to “Programmable
Signal Inputs” in the Powerware 9355 UPS
(10/15 kVA) User’s Guide
.

Serial Port Config

Port: [X-Slot-1] [X-Slot-2/Serv]
Speed: [19200] [9600] [2400] [1200]

19200

Modem Config

Modem Installation

Set Modem Call Events

Event #0
Call modem: no

Set Modem Init String

ATZ0

Set Modem Call Command

None

Set Modem Communication Password

None