9355 Parallel UPS (10/15 kVA) User’s Guide

S 164201601 Rev A www.powerware.com

51

Chapter 9

Parallel Bypass

To switch the parallel UPS to maintenance bypass from Normal mode:

1.

From any UPS, set the system to internal Bypass mode:

S

Using the

button on the front panel display, scroll to the Control

menu option and press the

button.

S

Press the

button to select the Go to Bypass Mode option.

The

and

indicators illuminate, indicating the UPS system

is operating in Bypass mode.

2.

Switch the bypass breaker on the parallel tie cabinet to the ON
position.

3.

Switch the UPS breakers on the parallel tie cabinet to the OFF
position.