Configuring the UPS for EBMs

NOTE Each UPS in a parallel system must have its own EBM and the same number of
EBMs to ensure consistent runtimes.

To ensure maximum battery runtime, configure the UPS for the correct
number of EBMs:

1.

Press any button on the front panel display to activate the menu
options.

2.

Using the

button, scroll to the Settings menu.

3.

Press the

button twice to select the User Settings menu.

4.

Using the

button, scroll to the Number of Battery Strings option

and press the

button.

5.

Use the

or

buttons to select the number of strings according to

your UPS configuration:

All 2-High UPS and EBM Cabinets*

Number of Strings

UPS + 1 EBM

6

UPS + 2 EBMs

10

UPS + 3 EBMs

14

UPS + 4 EBMs

18

All 3-High UPS and EBM Cabinets*

Number of Strings

UPS + 1 EBM

10

UPS + 2 EBMs

16

UPS + 3 EBMs

22

*UPS-32 models contain 2 strings; EBM-64 models contain 4 strings.
UPS-64 models contain 4 strings; EBM-96 models contain 6 strings.

6.

Press the

button to save the setting.

7.

Press the

ESC

button until the Eaton Powerware logo appears.