Troubleshooting – Lochinvar ArmorX2 1.5 User Manual

Page 48

background image

3

Troubleshooting

48

Table 3E (continued from previous page) Troubleshooting Chart - Fault Messages Displayed on Water Heater Interface

FAULT

DESCRIPTION

CORRECTIVE ACTION

Internal Fault

The main control board has detected an
internal fault.

• Replace the main control board.

Writing to

Memos

The main control board has detected an
internal fault.

• Replace the main control board.

CRC Parameters

The main control board has detected an
internal fault.

• Replace the main control board.

No Error Stored

The main control board has detected an
internal fault.

Press the RESET button on the SMART

TOUCH display panel.

Flue Temp

Shutdown

The stack temperature has exceeded the
set parameters for the water heater.

• Inspect the heat exchanger. Reference page 36 of
this manual for the procedure on how to clean the
flue side of the heat exchanger.

• Inspect the flue sensor and associated wiring.
Measure the resistance of the flue sensor and
compare to Table 3C on page 40 of this manual.
Replace the sensor if necessary.

• Verify that the vent/air intake pipes are properly
installed and that there are no obstructions.

• Replace the main control board.

Delta T

Shutdown

The temperature rise across the heat
exchanger has exceeded the set parameters
for the water heater.

• Verify that the system is full of water and that all air
has been properly purged from the system.

• Verify that the heater is piped properly into the heating
system. Refer to Section 6 - System Piping of the
Armor X2 Installation and Operation Manual
for the proper piping methods for the Armor X2 water
heater.

• Check for voltage to the water heater pump motor
on a call for heat. If voltage is not present, check
the wiring back to the pump relay. Replace the pump
relay if necessary.

• If 120 VAC is present on a call for heat and the water
heater pump is not operating, replace the pump.

• Verify that the water heater pump is set to the proper
speed or that the pump is the proper size. Reference
Section 6 - System Piping of the Armor X2 Water
Heater Installation and Operation Manual for water
heater pump specifications.

Outlet Temp

Shutdown

Outlet water temperature has exceeded the
maximum outlet water temperature.

• Verify that the system is full of water and that all air
has been properly purged from the system.

• Verify that the water heater is piped properly into the
heating system. Refer to Section 6 - System Piping
of the Armor X2 Installation and Operation Manual
for the proper piping methods for the Armor X2 water
heater.

• Check for voltage to the water heater pump motor on
a call for heat. If voltage is not present, check wiring
back to the pump relay. Replace the pump relay if
necessary.

• If 120 VAC is present on a call for heat and the heater
pump is not operating, replace the pump.

Service Manual