Table 3A Troubleshooting Chart - No Display

FAULT

CAUSE

CORRECTIVE ACTION

No Display

- No 120 VAC supplied to unit.

• Check external line switch, fuse, or breaker.

• Check position of ON/OFF switch. Turn switch to the
ON

position.

• Check 120 VAC through the ON/OFF switch.

• Check wiring harness connection between display

board and main control board. Connect

harness at both points.

- No voltage through the switch.

• Replace switch.

- Bad display board.

• Replace board.

- Bad main control board.

• Replace the main control board.

- Blown fuse.

• Replace fuse F3 on the main control board, see

page 38 of this manual.

No Burner

Operation

- Main control board temperature set point
satisfied.

• Review temperature setting.

- Remote thermostat satisfied.

• Review remote thermostat setting.

- Unit locked out on fault.

• Consult display for specific fault. Refer to fault

descriptions on page 42 of this manual for corrective
actions.

Unit Does

Not Modulate

Above 50%

- Water heater controlled by BMS.

• Check BMS parameter settings.

- Flue sensor open.

• Verify that the flue sensor is located in the flue outlet.

• Check wiring connections at the flue sensor.

• Check the resistance of the flue sensor and compare
to Table 3C on page 40 of this manual.