Table 3E (continued from previous page) Troubleshooting Chart - Fault Messages Displayed on Water Heater Interface

FAULT

DESCRIPTION

CORRECTIVE ACTION

Automatic Reset

High Limit / HEX-

Temp SW

(will require a manual

reset once the condition

has been corrected. Press

the RESET button on the

display to reset.)

Either the auto-reset high limit, or the
O-temp heat exchanger switch has opened.

Automatic Reset High Limit:

• Verify that the system is full of water and that all air
has been properly purged from the system.

• Verify that the water heater is piped properly into the
heating system. Refer to Section 6 - System Piping
of the Armor X2 Installation and Operation Manual for
the proper piping methods for the Armor X2.

• Check voltage to water heater pump motor on a call
for heat. If voltage is not present, check wiring back
to the pump relay.

• Replace the pump relay if necessary.

• If 120 VAC is present on a call for heat and the water
heater pump is not operating, replace the pump.

• Check resistance of water sensors and compare to
Table 3B on page 40 of this manual. Replace sensor
if

necessary.

• Replace outlet sensor.

HEX Temp SW:

• Check continuity across two contacts. Wires should
be connected at both poles of normally closed switch.


• Inspect the rear of the inner combustion chamber
at the burner level, for refractory breakdown/missing.
Replace the refractory if no damage to the heat
exchanger as a result of the burner, otherwise,
replace the heat exchanger.

• Faulty O-temp heat exchanger switch. Replace
switch.

Blower RPM’s

Too Low

(will require a manual

reset once the condition

has been corrected. Press

the RESET button on the

display to reset.)

The actual fan rpm is 30% lower than what
is being called for. Reference the Burners
Screen information on page 28 of this
manual.

• Vent/air intake lengths exceed the maximum allowed
lengths. Refer to Section 3 - General Venting of the
Armor X2 Installation and Operation Manual for
proper

lengths.

• Check for obstruction or blockage in the vent/air
intake pipes or at terminations.

• Check the wiring connections at the fan and at the
main control board.

• Replace the fan.

• Replace the main control board.

Blown fuse.

• Replace fuse F4 on the control board, see page 38 of
this

manual.