Page 33: Inspect water heater interior, Clean condensate trap, Check all piping for leaks

background image

Follow the service and maintenance procedures given throughout this manual and in component literature
shipped with the water heater. Failure to perform the service and maintenance could result in damage to the
water heater or system. Failure to follow the directions in this manual and component literature could result
in severe personal injury, death, or substantial property damage.

The water heater should be inspected annually only by a qualified service technician. In addition, the
maintenance and care of the water heater designated in Table 2A and explained on the following pages must
be performed to assure maximum water heater efficiency and reliability. Failure to service and maintain the
water heater and system could result in equipment failure.

Electrical shock hazard – Turn off power to the water heater before any service operation on the water heater
except as noted otherwise in this instruction manual. Failure to turn off electrical power could result in
electrical shock, causing severe personal injury or death.

Address reported problems

1. Inspect any problems reported by the owner and correct

before proceeding.

Inspect water heater area

1. Verify that water heater area is free of any combustible

materials, gasoline and other flammable vapors and
liquids.

2. Verify that air intake area is free of any of the contaminants

listed in Section 1 of the Armor X2 Installation and
Operation Manual. If any of these are present in the
water heater intake air vicinity, they must be removed.
If they cannot be removed, reinstall the air and vent
lines per this manual and the Armor X2 Installation and
Operation Manual.

Inspect water heater interior

1. Remove the front access cover and inspect the interior of

the water heater.

2. Vacuum any sediment from inside the water heater and

components. Remove any obstructions.

Clean condensate trap

1. Inspect the condensate drain line, condensate PVC

fittings, and condensate trap.

2. Remove the PVC cap retaining screw from the PVC cap

(FIG. 2-1).

3. Remove the 2 inch PVC cap with the switch located at the

top of the trap (FIG. 2-1).

4. Remove any sediment in the trap.

5. Fill with fresh water until the water begins to pour out of

the drain.

6. Replace the cap. Press the cap onto the trap until the cap

makes contact with the drain.

7. Replace the retaining screw.

Eliminate all system or water heater leaks.
Leaking water may cause severe property
damage.

1. Inspect all water and gas piping and verify to be leak free.

2. Look for signs of leaking lines and correct any problems

found.

3. Check gas line using the procedure found in Section 7

- Gas Connections of the Armor X2 Installation and
Operation Manual.

Check all piping for leaks

The condensate trap must be filled with
water during all times of water heater
operation to avoid flue gas emission from
the condensate drain line. Failure to fill
the trap could result in severe personal
injury or death.

ƽ WARNING

ƽ WARNING

ƽ WARNING

ƽ WARNING

ƽ WARNING

CONDENSATE FROM

HEAT EXCHANGER

RETAINING

SCREW

2” PVC CAP WITH

BLOCKED DRAIN SWITCH

PVC TEE ASSEMBLY

(FACTORY SUPPLIED)

TO FLOOR

DRAIN

Figure 2-1 Condensate Trap

2

Maintenance

(continued)

33

Service Manual