Inspect ignition and flame sense

electrodes

1. Remove the ignition and flame sense electrodes from the

water heater heat exchanger access cover.

2. Remove any deposits accumulated on the ignition/flame

sense electrode using sandpaper. If the electrodes cannot
be cleaned satisfactorily, replace with new ones.

3. Replace ignition/flame sense electrode, making sure

gasket is in good condition and correctly positioned.

Check ignition ground wiring

1. Inspect water heater ground wire from the heat exchanger

access cover to ground terminal strip.

2. Verify all wiring is in good condition and securely

attached.

3. Check ground continuity of wiring using continuity

meter.

4. Replace ground wires if ground continuity is not

satisfactory.

Check all water heater wiring

1. Inspect all water heater wiring, making sure wires are in

good condition and securely attached.

Check control settings

1. Go to the Setup Screen and check all settings. See Section

1 of this manual. Adjust settings if necessary. See Section
1 of this manual for adjustment procedures.

2. Check settings of external limit controls (if any) and

adjust if necessary.

Perform start-up and checks

1. Start water heater and perform checks and tests specified

in Section 9 - Start-up of the Armor X2 Installation and
Operation Manual.

Check burner flame

1. Inspect flame through observation window.

2. If the flame is unsatisfactory at either high fire or low

fire, turn off water heater and allow water heater to cool
down. Remove the burner and clean it thoroughly using a
vacuum cleaner or compressed air. Do not use compressed
air to clean burner if performed inside a building.

3. Remove the burner, reference FIG. 2-2.

4. When replacing the burner, ensure gasket is in good

condition and positioned correctly (FIG. 2-2).

BURNER

AIR/GAS GASKET

FLAPPER VALVE

BURNER DOOR

BURNER DOOR

HEX NUT (6)

IGNITER

FLAME SENSE

IGNITER GASKET

FLAME SENSE

GASKET

FLAME SENSE

SCREW (2X)

IGNITER SCREW (2X)

DOOR FIBER

FLAPPER VALVE

SCREW (5X)

Figure 2-2 Burner Assembly

2

Maintenance

(continued)

35

Service Manual

Check flame signal

1. At high fire the flame signal shown on the display should be

at least 10 microamps.

2. A lower flame signal may indicate a fouled or damaged

flame sense electrode. If cleaning the flame sense electrode
does not improve, ground wiring is in good condition, and
ground continuity is satisfactory, replace the flame sense
electrode.

3. See Section 3 - Troubleshooting in this manual for other

procedures to deal with low flame signal.

Review with owner

1. Review the Armor X2 Installation and Operation Manual

with the owner.

2. Emphasize the need to perform the maintenance schedule

specified in the Armor X2 Installation and Operation
Manual (and in this manual as well).

3. Remind the owner of the need to call a licensed contractor

should the heater or system exhibit any unusual behavior.