Troubleshooting – Lochinvar ArmorX2 1.5 User Manual
Page 44

3
Troubleshooting
44
Table 3E (continued from previous page) Troubleshooting Chart - Fault Messages Displayed on Water Heater Interface
FAULT
DESCRIPTION
CORRECTIVE ACTION
Flame Lost
While Running
(cont’d)
(will require a
manual reset once the
condition has been
corrected. Press the
RESET button on the
display to reset.)
The unit was running and lost the flame 
signal. This condition occurred twice .
• If 24 VAC is present at the main control board, check 
 the wiring between the main control board and the gas 
 valve. Replace the wiring if necessary. Do not 
 disconnect the wiring from the gas valve and attempt 
 to measure voltage at that point. The main control 
 board can detect if the gas valve is not connected and 
 will display the Gas Valve / Connection fault.
• If 24 VAC is present, check the outlet of the valve to 
 ensure the valve is flowing gas. With a manometer 
 connected to the outlet tap of the gas valve, when the 
 unit is in the prepurge period, there should be a 
 negative pressure present. When the valve is 
 energized a change in pressure should occur. If the 
 pressure change does not occur, the gas valve is not 
 opening. Replace the gas valve.
•
Inspect flame sensor and associated wiring.
 Reference page 35 of this manual for removal and 
 cleaning procedures. Replace if necessary.
• Inspect the burner. Reference page 35 of this manual 
 for removal and cleaning procedures. Replace if 
 necessary.
• Replace the main control board.
Manual Reset
High Limit
(will require a
manual reset once the
condition has been
corrected. Press the
RESET button on the
display to reset.)
The outlet water temperature has exceeded 
the setting of the high limit.
• Verify that the system is full of water and that all air 
 has been properly purged from the system.
• Verify that the water heater is piped properly into the 
 heating system. Refer to Section 6 - System Piping 
 of the Armor X2 Installation and Operation Manual 
 for the proper piping methods for the Armor X2.
• Check voltage to water heater pump motor on a call for 
 heat. If voltage is not present, check wiring back to 
 the pump relay. 
• Replace the pump relay if necessary.
• If 120 VAC is present on a call for heat and the water 
 heater pump is not operating, replace the pump.
• If the high limit has tripped, check setting of the 
 device.
• Check resistance of water sensors and compare to 
 Table 3B on page 40 of this manual. Replace sensor 
 if 
necessary.
• Replace high limit.