Troubleshooting – Lochinvar ArmorX2 1.5 User Manual

Page 47

background image

Table 3E (continued from previous page) Troubleshooting Chart - Fault Messages Displayed on Water Heater Interface

FAULT

DESCRIPTION

CORRECTIVE ACTION

Air Flow Too

Low

(will require a manual

reset once the condition

has been corrected.

Press the RESET button

on the display to reset.)

Air pressure switch contacts are open.

• Check the wiring connections to switch. Wires should
be connected to the common and normally closed
terminals.

• Vent/air intake lengths exceed the maximum allowed
lengths. Refer to Section 3 - General Venting of the
Armor X2 Installation and Operation Manual for
proper

lengths.

• Check for obstruction or blockage in the vent/air
intake pipes or at terminations.

• Check reference hoses connected to the air pressure
switch for blockage or obstruction.

• Inspect the burner. Reference page 35 of this manual
for removal and cleaning procedures. Replace if
necessary.

• Inspect the heat exchanger. Reference page 36 of
this manual for removal and cleaning procedures.
Replace if necessary.

• Faulty air pressure switch. Replace switch.

Flap valve contacts are in an open position.

• Check the wiring connections to the flap valve switch.
Replace or repair wiring if necessary.

• Check for obstruction in the vent / air intake pipes or
at

terminations.

• Verify combustion air blower is operating. Replace if
necessary.

• Replace flap valve switch.

Flap Valve

Stuck Open

Flap valve contacts are in a closed position.

• Check wiring connections to the flap valve switch.
Replace or repair wiring if necessary.

• Check flap valve for obstruction or blockage.

• Replace flap valve switch.

Too Many

Resets - Try Later

Too many manual resets have occurred
during a 15 minute period.

• Wait 15 minutes and try again.

• Turn power off to unit, wait 30 seconds and then turn
power back on.

Voltage Too

Low

120 VAC input to the main control board has
dropped below 80 VAC.

• Check 120 VAC supply to the transformer.

• Check wiring connections at the low voltage terminal
strip.

• Check the wire size/length to remote devices.

• Replace the main control board.

47

3

Troubleshooting

(continued)

Service Manual