Troubleshooting

38

Label all wires prior to disconnection when
servicing controls. Wiring errors can
cause improper and dangerous operation.
Always disconnect power to the water
heater before servicing. Failure to comply
could result in severe personal injury,
death, or substantial property damage.

Never jumper (bypass) any device except
for momentary testing as outlined in the
Troubleshooting chart. Severe personal
injury, death, or substantial property
damage can result.

Before troubleshooting:

1. Have the following items:

a.

Voltmeter that can check 120 VAC, 24 VAC, and

12

VDC.

b. Continuity

checker.

c. Contact

thermometer.

2. Check for 120 VAC (minimum 102 VAC to maximum

132 VAC) to water heater.

3. Make sure all external limit controls are installed and

operating.

Check the following:

1. Wire connectors to control module are securely plugged

in at the control module and originating control.

2. Gas

pressures:

• Maximum: 14 inches w.c. (3.5 kPa) natural,
14 inches w.c. (3.2 kPa) LP with no flow (lockup)
or with water heater on
• Minimum: 4 inches (5 inches on 1.0 models only) w.c.
(1.0 kPa) natural, 8 inches w.c. (2.0 kPa) LP with gas
flowing (verify during water heater startup)

Check control module fuses

ALWAYS check control module fuses
before replacing control module or any
major components (blower, etc.). If one
of these fuses is blown, it can prevent the
control module or other components from
operating.

1. Turn OFF the power to the water heater at the external
line

switch.

2. Remove the front access cover.

3. Remove the two (2) screws securing the control panel to

the unit to gain access to the control module.

F4 - 3.15 AMP FUSE

BLOWER

F3 - 1.25 AMP FUSE

MAIN BOARD

F5 - 5 AMP FUSE

PUMPS

F2 - 3.15 AMP FUSE

24V SUPPLY

Figure 3-1 Control Module Fuses

4. Remove the two (2) nuts on the control module cover.

5. Inspect fuses F2, F3, F4, and F5, see FIG 3-1 below.

6. The water heater is shipped with six (6) spare fuses in

a plastic bag located under the low water cutoff on the
control module.

7. If necessary, replace open fuse (F3 is 1.25 amps, F2 and F4

are 3.15 amps, and F5 is 5 amps).

Note: Fuses F2 - F5 are all slow blow fuses.

Do not jumper fuse or replace with any
fuse except as specified. Failure to comply
could result in severe personal injury,
death, or substantial property damage.

8. Re-install the control module cover using the nuts

removed in Step 4.

Note: If the spark wire was unplugged, reattach it to the

control.

9. Re-install the control panel using the two (2) screws

removed in Step 3. Re-install the front access cover after
fuse inspection.

10. Restore power to the water heater at the external line

switch and verify water heater operation (Section 9 -
Start-up in the Armor X2 Installation and Operation
Manual) after completing water heater service.