Troubleshooting – Lochinvar ArmorX2 1.5 User Manual
Page 41

3
Troubleshooting
(continued)
41
Table 3D Troubleshooting Chart - Noisy System
FAULT
CAUSE
CORRECTIVE ACTION
Noisy
Operation
- Supply gas problem. Natural gas pressures 
 should be between 4 inches w.c. (1.0 kPa) 
 and 14 inches w.c. (3.5 kPa). LP gas 
 pressures should be between 8 inches w.c. 
 (2.0 kPa) and 14 inches w.c. (3.2 kPa).
 • Refer to Section 7 - Gas Connections of the Armor X2 
 Installation and Operation Manual for detailed 
 information concerning the gas supply.
- Gas/air mixture problem.
• Refer to the Gas Valve Adjustment Procedure on
 page 50 of this manual for the proper gas valve setting. 
 Verify that the vent/air intake lengths do not exceed the 
 maximum listed in the General Venting section of the 
 Armor X2 Installation and Operation Manual.
- Dirty/damaged burner.
 • Refer to page 35 in this manual for the burner removal 
 and inspection procedure. Clean or replace the burner 
 as 
necessary.
- Low water flow through the heat exchanger.
•
Refer to Section 6 - System Piping of the
 Armor X2 Installation and Operation Manual for 
 minimum flow rates. Verify that the water heater is piped 
 in a primary/secondary fashion and that the water heater 
 and system pump are running on a call for heat.
- Air in the piping system.
• Properly purge all air from the piping system.
- Low system water pressure.
•
Verify system pressure is a minimum of 12 psi
(82.7
kPa).
No Pump
Operation -
HW Pump
- Blown fuse.
 • Replace fuse F5 on the control board, see page 38 of 
 this 
manual.
- Faulty pump.
• Replace pump.
- Internal fault on control board.
• Replace main control board.
- Faulty pump relay.
• Replace relay.
Relief Valve
Opening
-
System pressure exceeds relief valve
setting.
•
Lower the system pressure below the 150 psi
(1034.2 kPa) rating of the supplied relief valve.
• Improperly sized expansion tank.
- Outlet temperature exceeds relief valve 
 settings.
• Check temperature settings of the main control board.
Service Manual