1

Determine boiler location

(continued)

Products to avoid:

Spray cans containing chloro/fl uorocarbons

Permanent wave solutions

Chlorinated waxes/cleaners

Chlorine-based swimming pool chemicals

Calcium chloride used for thawing

Sodium chloride used for water softening

Refrigerant leaks

Paint or varnish removers

Hydrochloric acid/muriatic acid

Cements and glues

Antistatic fabric softeners used in clothes dryers

Chlorine-type bleaches, detergents, and cleaning solvents
found in household laundry rooms

Adhesives used to fasten building products and other
similar products

Areas likely to have contaminants

Dry cleaning/laundry areas and establishments

Swimming pools

Metal fabrication plants

Beauty shops

Refrigeration repair shops

Photo processing plants

Auto body shops

Plastic manufacturing plants

Furniture refi nishing areas and establishments

New building construction

Remodeling areas

Garages with workshops

Table 1A Corrosive Contaminants and Sources

Provide clearances:

Clearances from combustible materials
1. Hot water pipes—at least 1/4" (6 mm) from combustible

materials.

2. Jacket—minimum of 0" from right side and 14" from rear

side for proximity from combustible materials.

3. Vent—minimum of 1" from combustible materials.

Clearances for service access
1. If you do not provide the minimum clearances shown, it

may not be possible to service the boiler without removing

it from the space.

Do not install the boiler on carpeting even
if foundation is used. Fire can result,
causing severe personal injury, death, or
substantial property damage.

Flooring and foundation

Flooring

The Outdoor Knight XL is approved for installation on
combustible fl ooring.

ƽ WARNING

Prevent combustion air contamination

Do not install unit in locations that can allow contamination
of combustion air. Refer to Table 1A for products and areas
which may cause contaminated combustion air.

Under no circumstances is the manufacturer to be held
responsible for water damage in connection with this
appliance, or any of its components. If fl ooding is possible,
elevate the boiler suffi ciently to prevent water from reaching
the boiler.

Recommended service clearances
Front: 30" (762mm)
Top: 24" (610mm)
Left side: 24" (610mm)
Rear: 24" (610mm)

Outdoor Knight XL Installation & Operation

Manual

Outdoor vent / air intake location:

The fl ue products discharged from the
fl ue outlet on the outdoor vent may be
very hot. Avoid touching or making other
direct contact with the fl ue gases or the
vent termination. These components are
hot and direct contact can result in burns.

ƽ WARNING

To prevent recirculation of the fl ue products into the
combustion air inlet, follow all instructions in this section.

Flue gas condensate can condense on exterior walls or on the
vent. Some discoloration or exterior building or unit surfaces
can be expected. Adjacent brick or masonry surfaces should
be protected with a rust resistant sheet metal plate.

Maintain a minimum of 24" clearance to the air inlet.

Locate the outdoor vent termination at least 48" (1.22m)
below and 48" (1.22m) horizontally from any window, door,
walkway or gravity air intake.

Locate the unit at least 10 feet (3.05m) away from any forced
inlet.

Multiple unit outdoor installations require 24" (1.22m)
clearance between each vent termination.

Clearances around outdoor installations can change with
time. Do not allow the growth of trees, shrubs or other plants
to obstruct the proper operation of the outdoor vent system.