beautypg.com

Prepare boiler – Lochinvar Kight XL 400-801 User Manual

Page 11

background image

2

Prepare boiler

(continued)

Outdoor Knight XL Installation & Operation

Manual

Do NOT use grease or other lubricant on the
vent seals. Only water may be used for this
purpose. Grease or other lubricant can make
the seal brittle or cause tearing of the seal
surface which can result in fl ue gas leakage.

ƽ CAUTION

11

Models 701 - 801

Figure 2-3 Install fl ue pipe assembly - Models 701 - 801

CLAMP

VENT COVER

WALL STRAP

SCREWS

WALL

STRAP

ELBOW

VENT PIPE

VENT

TERMINATION

IMG00446

NOTE: VERIFY THAT GASKET IS SEATED EVENLY
INSIDE THE GROOVE IN ELBOW AND ADAPTER

1. Locate all venting components from the installation kit and

carton.

2. Before connecting the vent pipe sections or components,

verify that the gasket is seated evenly inside the groove
in the female end of the elbow and fl ue adapter
(FIG. 2-3).

3. Remove the vent cover from the back of the unit as shown in

FIG. 2-3.

4. Insert the elbow into the fl ue adapter and tighten the clamp

using a 5/16" nut driver (FIG. 2-3).

5. Re-install the vent cover removed in Step 3.

6. Remove the provided screws from the vent cover and use

them to install the wall strap (FIG. 2-3).

7. Slide the vent pipe through the wall strap and insert it into the

elbow. Tighten the clamp (FIG. 2-3).

8. Install the termination into the top of the vent and tighten the

clamp.