Ratings

Notes:

1. The ratings are based on standard test procedures prescribed by the United States Department of Energy.

2. Net AHRI ratings are based on net installed radiation of suffi cient quantity for the requirements of the building and nothing

need be added for normal piping and pickup. Ratings are based on a piping and pickup allowance of 1.15.

3. Standard Outdoor Knight XL boilers are equipped to operate from sea level to 4,500 feet only with no adjustments. The boiler

will de-rate by 4% for each 1,000 feet above sea level up to 4,500 feet.

4. Ratings have been confi rmed by the Hydronics Section of AHRI.

5. Outdoor Knight XL boilers comply with the requirements of CSD-1 Section CW-400 requirements as a temperature operation

control. The manual reset high limit provided with the Outdoor Knight XL is listed to UL353.

Maximum allowed working pressure is located on the rating plate.

NOTICE

Outdoor Knight XL Boiler

AHRI Rating

Model Number

Note: Change “N” to

“L” for L.P. gas models.

Input
MBH

(Note 4)

Min Max

Gross

Output

MBH

(Note 1)

Net

AHRI

Ratings

Water,

MBH

(Note 2)

OKN400

80

399

370

322

OKN501

100

500

463

402

OKN601

120

600

566

493

OKN701

140

700

658

572

OKN801

160

800

748

651

Other Specifi cations

Boiler Water

Content

Gallons

Water

Connections

Gas

Connections

Air Size

3.4

1-1/2"

1"

4"

4.2

1-1/2"

1"

4"

4.2

2"

1"

4"

5.0

2"

1"

4"

5.7

2"

1"

4"

Outdoor Knight XL Installation & Operation