Maintenance and annual startup

Table 9A Service and Maintenance Schedules

Owner maintenance

(see the Outdoor Knight XL User’s Information

Manual for instructions)

Daily

• Check boiler area

Check pressure/temperature

gauge

Monthly


Check air and vent termination

screens

• Check relief valve

• Check condensate drain system

Periodically

• Test low water cutoff (if used)

• Reset button (low water cutoff)

Every

6 months

• Check boiler piping (gas and

water) for leaks

• Operate relief valve

End

of season

months

• Shut boiler down (unless boiler

used for domestic hot water)

9

Maintenance

Service technician

(see the following pages for instructions)

General:

• Address reported problems

• Inspect interior; clean and vacuum if

necessary;

• Clean condensate trap and fi ll with fresh

water

Check for leaks (water, gas, fl ue,

condensate)

Verify

fl ue and air passage ways in good

condition and sealed tight

• Check system water pressure/system

piping/expansion

tank

• Check control settings

Check ignition and flame sense

electrodes (sand off any deposits; clean

and

reposition)

• Check wiring and connections

Perform start-up checkout and performance

verifi cation per Section 7.

• Flame inspection (stable, uniform)

• Flame signal (at least 10 microamps at

high

fi re)

Clean the heat exchanger if fl ue temperature

is more than 54°F (30°C) above return water
temperature.

If combustion or performance
indicate need:

• Clean heat exchanger

Remove and clean burner using

compressed air only

• Clean the blower wheel

ANNUAL START-UP

Outdoor Knight XL Installation & Operation

Manual