Operating information – Lochinvar Kight XL 400-801 User Manual
Page 44

44
8
Operating information
Outdoor Knight XL Installation & Operation
Manual
OPERATION
DISPLAY
8. If the space heating call for heat is active, and the tank thermostat
or sensor starts a DHW call for heat, the boiler will switch to the 
DHW mode. If programmed for normal DHW operation (not as a 
zone), the DHW pump will turn on fi rst, then the boiler pump will 
turn off (boiler and DHW pump operation briefl y overlap to ensure 
fl ow is maintained through the unit). This will divert the boiler’s 
outlet water from the heating system and send it to the tank coil 
instead. The control will then modulate to maintain the outlet 
temperature to the DHW boiler set point.
9. If the boiler is not part of a Cascade, and both the space heating
and DHW calls for heat remain active long enough, the boiler will 
switch back and forth between the two heating modes until one of 
them is satisfi ed.
10. Once both calls for heat are satisfi ed, the control will turn off
 the burner.The blower will continue to run during the postpurge 
 period.
11. Any pumps that are running will continue to run for their respective
pump delay times before turning off, unless programmed to 
remain on continuously. A 60 second anti-cycle period will start, 
which will delay any new call for heat until it times out.
12. In Standby, ready to start a new cycle.
Sequence of operation