Hydronic piping

(continued)

Near boiler piping connections

Y-STRAINER

(RECOMMENDED)

BOILER PUMP

INDIRECT
DOMESTIC
HOT WATER
TANK

TO FLOOR
DRAIN

TO

FR

OM

FR

OM

SY

ST

EM

TO

SY

ST

EM

DOMESTIC HOT
WATER PUMP

AIR SEPARATOR

SYSTEM SENSOR

IMG00413

SYSTEM PUMP

Figure 3-4A Near Boiler Piping w/Y-Strainer

Circulator sizing

The Outdoor Knight XL heat exchanger does have a pressure
drop, which must be considered in your system design. Refer
to the graphs in FIG’s 3-5 and 3-6 for pressure drop through
the Outdoor Knight XL heat exchanger.

DRAIN
(TYPICAL)

AIR SEPARATOR

AIR VENT VALVE

EXPANSION TANK

LOW LOSS HEADER
(TYPICAL)

Y-STRAINER

(RECOMMENDED)

DRAIN
VALVE

FAST FILL VALVE

INDIRECT
DOMESTIC
HOT WATER
TANK

SYSTEM SENSOR

SYSTEM PUMP

TO FLOOR
DRAIN

TO

FR

OM

FR

OM

SY

ST

EM

TO

SY

ST

EM

BOILER PUMP

IMG00391

Figure 3-4B Near Boiler Piping w/Low Loss Header

12. Boiler purge valve:

Field supplied. The boiler purge valve is used to

remove entrapped air from the heat exchanger during

start-up.

13. System temperature sensor:

Lochinvar supplies a system temperature sensor. The

sensor is to be installed in the heating loop downstream

from the boiler hot water piping and heating loop

junction. The sensor should be located far enough

downstream to sense system diluted water temperature.

14. Y-Strainer:

Field supplied. A Y-strainer or equivalent multipurpose

strainer is recommended at the inlet of the heat exchanger

to remove system particles from older hydronic systems

and protect newer systems.

Variable speed pump option

Variable speed pump setup

Before operation, ensure the following:

-

Pump is set for an input signal of 0 - 10VDC

by the dip switches on the pump control

- Pump is set for external signal control

(if

applicable)

-

Pump is set for linear output (if applicable)

- If pump does not come equipped with a

0 - 10 VDC input option, an optional module

will be required from the vendor

SMART SYSTEM / Multi-temperature

loop control option

The Outdoor Knight XL boiler is capable of producing
up to three (3) set point temperatures to meet different
space heating demands. When using more than one
temperature demand it is necessary to protect the
lower temperature loop from overheating. To help
aid with this protection, Lochinvar offers the Multi-
Temperature Loop Control Board Kit (RLY30086).

Outdoor Knight XL Installation & Operation