beautypg.com

4 connections without assignment – Siemens Simantic Net NCM for Industrial Ethernet S7 User Manual

Page 97

background image

Configuring Communication Connections

97

SIMATIC NET NCM S7 for Industrial Ethernet
C79000-G8976-C129–06

4.3.4

Connections Without Assignment

Overview

This section explains the actions that can lead to a configured connection losing its
assignment to the CP or being deleted.

Caution

Remember that in contrast to the S7 connections, the connections of the
SEND/RECEIVE interface are assigned a CP-dependent ID. The actions below
may require the ID to be modified so that the interface information in the user
program must also be adapted.

Table 4-3

Actions That Can Cause Changes to Configured Connections

Action

Consequences for the

Connections

How to Establish the Connection

Again

The CP (module) is
moved to a different
location in the hardware
configuration (drag and
drop)

The connections are retained.

The connection IDs are
automatically updated.

1. Adapt the module start address

LADDR in the user program.

2. Download the connection

configuration to the CP again.

The CP (module) is
deleted in the hardware
configuration.

You receive the message
“CP has n connections;
the assignment will be lost
in the connection table”.

The connections remain without
assignment to a CP
in the
connection table. In the
“Overview” tab of the Properties
dialog, the connections are
identified with “!”.

Once you have placed a CP in the
hardware configuration and networked it:

1. Assign the CP in the connection

properties dialog in the “Addresses”
tab.
or
Reassign the connection using the
menu option Edit

"

Connection

Partner....

2. Adapt the connection ID in the user

program.

3. Download the connection

configuration to the CP again.

Deleting the SIMATIC S7
station.

All the connections to this station
are deleted within the project.

Reconfigure the station and
connections.