Configuring Communication Connections

106

SIMATIC NET NCM S7 for Industrial Ethernet

C79000-G8976-C129–06

Attributes

Access

Description

Inactivity Time

The inactivity time specifies the interval after which
the connection is terminated if no sign of life is
received from the partner (6–180 s, default 30 s).

Modifiable

Window Time

The window time specifies the interval at which sign
of life frames are sent. For SIMATIC NET CPs, the
window time is set to 1/3 of the inactivity time (2–60
s, default 10 s). Sign of life frames are sent to check
the connection when there is no data traffic.

Display only

Notice

Window Time and Inactivity Time
The partner responds to a sign of life frame with a frame. They are therefore sent
to the partner at the intervals of the window time. To avoid unwanted connection
termination, the inactivity time should be at least three times as long as the
window time.