Programming FCs (Functions) and FBs for S7 Ethernet CPs

156

SIMATIC NET NCM S7 for Industrial Ethernet

C79000-G8976-C129–06

Parameter

Remarks

Possible

Values

Type

Declara-
tion

LEN

INPUT

INT

On ISO
Transport and
ISO-on-TCP /
TCP:

1 2 t 32767

Number of bytes to be sent from the data area
with this job. The possible values range from 1
to length specified for the SEND parameter.

S

Note the block type:

1,2, to 32767
(or up to “length
specified for
SEND
parameter”)

On UDP:

1,2,...2048 (or

S7-300

With older versions of FC AG_SEND
(up to V3.0), the data area is always
restricted to a maximum of 240 bytes.

The current versions allow up to 8192
bytes (2048 bytes for UDP).

1,2,...2048 (or
up to “length
specified for
SEND
parameter”)

S7-400

With FC AG_SEND, the data area is
restricted to a maximum of 240 bytes.

S

Note on the S7-400:
Data transfer may be restricted to
LEN<=240 bytes with older versions of the
CP firmware!

For further information, see /1/

S

Improved performance with shorter data
records:

Transfer of data records up to 240 bytes
results in better performance regardless of
the block type used.

DONE

OUTPUT

BOOL

0: Job active
1: done

This parameter indicates whether or not the job
was completed without errors.
As long as DONE = 0, no further job can be
triggered. DONE is set to 0 by the CP when it
accepts a new job.
For the meaning of this parameter in
conjunction with the ERROR and STATUS
parameters, refer to the following table.

ERROR

OUTPUT

BOOL

0: –
1: error

For the meaning of this parameter in
conjunction with the DONE and STATUS
parameters, refer to the follow table.

STATUS

OUTPUT

WORD

see following
table

Status code
The following table shows the condition codes
formed by the DONE and ERROR parameters.

Condition Codes

The following table shows the condition codes formed by the DONE, ERROR and
STATUS parameters that must be evaluated by the user program.