Siemens Simantic Net NCM for Industrial Ethernet S7 User Manual
Page 194
Firmware Loader
194
SIMATIC NET NCM S7 for Industrial Ethernet
C79000-G8976-C129–06
2nd Step
Select the interface via which you want to download the firmware.
The interface type (PROFIBUS or Industrial Ethernet) is already decided by the
load file you selected.
S
For a PROFIBUS module:
There are no further settings in this dialog; go to the next step.
S
For an Industrial Ethernet module:
Select or specify the MAC address of the Ethernet module and go to the next
step.
Note
The following applies to an Industrial Ethernet module:
If a download to the module was previously aborted, you must click the
Emergency Address button. In this case, it is assumed that module memory has
been reset and it is now only accessible using the emergency address.
With newer modules, a fixed MAC address assigned to the module is used
instead of an emergency address. Please refer to the information in the relevant
manual /1/ on the topic of “Downloading New Firmware”.
3rd Step
Check the configuration.
You can check and adjust settings for the PG/PC interface using the Modify...
button.
Set the PG/PC interface according to the CPs available on your PG (“Device
Parameter Assignments” list box) and according to the bus attachment
(“Properties” list box).
For more detailed information, refer to the integrated help system.
Continue to follow the instructions in the dialog to establish the connection to the
Ethernet CP.