Sanyo KHH2672R / CH2672R User Manual
Page 65

1
2
3
4
5
6
I-61
SM831148
1. Specifications
1-3 Other Component Specifications
(B) Outdoor Unit
MODEL No.
CH3072R, C3072R, CH3672R, C3672R
Thermistor (Coil sensor) : TH2 to 5
Coil resistance
k
Ω
14
°F : 23.7
,
50
°F : 9.7
23
°F : 18.8
,
68
°F : 6.5
32
°F : 15.0
,
86
°F : 4.4
41
°F : 12.1
,
104
°F : 3.1
113
°F : 2.6
Thermistor (Comp. discharge gas sensor) : TH6
Coil resistance
k
Ω
140
°F : 13.8
,
194
°F : 5.1
158
°F : 9.7
,
212
°F : 3.8
167
°F : 8.2
,
230
°F : 2.8
176
°F : 7.0
,
248
°F : 2.2
185
°F : 5.9
,
266
°F : 1.7
Solenoid coil or 4 way valve
4 way valve
STF - 02U2G
Solenoid coil
STF - 01AQ503UA1 (Heat pump models only)
DATA SUBJECT TO CHANGE WITHOUT NOTICE
Electric expansion valve (MOV)
Valve
UKV - 18D13
Coil
UKV - U013E
This manual is related to the following products: