3.other component specifications – Sanyo KHH2672R / CH2672R User Manual
Page 51

1
2
3
4
5
6
I-47
SM831148
1. Specifications
1-3 Other Component Specifications
(A) Indoor Unit
MODEL No.
XH2672R
Power Transformer
ATR – IIK224A
Rated
Primary
220 VAC, 60 Hz
Secondary
BRN - BRN : 14 V, 0.45 A, RED - RED : 14 V, 0.3 A
Capacity
—
Coil resistance
Ω
WHT - WHT
:
61.0
,
RED - RED
:
1.37
(Ambient temprature 77
°F)
BRN - BRN
:
0.97 ,
ORG - ORG
:
3.16
Thermistor cut off temperature
°F
277
Thermistor (Coil sensor) : TH2, 3
PBC - 41E - S14
Coil resistance
k
Ω
14
°F : 23.7
,
41
°F : 12.1
23
°F : 18.8
,
50
°F : 9.7
32
°F : 15.0
,
59
°F : 8.0
Thermistor (Room sensor) : TH1
KTEC - 35 - S6
Coil resistance
k
Ω
32
°F : 16.5
,
104
°F : 2.7
41
°F : 12.8
,
113
°F : 2.2
50
°F : 10.0
,
122
°F : 1.8
68
°F : 6.3
,
131
°F : 1.5
86
°F : 4.0
,
Drain pump
PJV - 1428AU
Rated
230 / 208 VAC, 12.5 W
Float switch
FS - 0218 - 102
MAX Rated (Contact rated)
50 W, DC 5V, 0.1 mA
Synchronized Motor
MT8 - 3C